Product Detail :
|
Supply of 33kv pt 33kv pt type- outdoor ,designation 33kv oil filed pt , reference to bis standard (s)- is3156, voltage -33kv(rated kv) ;36kv(highest kv, secondary core details- 1-no. of secondary core-one, 2- rated secondary voltage (s) v-100/1.7 , 3- rated output va - 100va ,4-classof accuracy -0.5 , maximum ratio error with rated burden ? as per is , maximum phase angle error with rated burden - as per is ,grade of insulating oil used - is335 ,temperature rise at 1.1 time rated voltage and rated burden ?as per is , rated voltage factor and time = 1.2continuous/1.5 for 30 sec, impulse withstand test voltage kvpeak= 170,1 minute power frequency with stand testvoltage of primary kvrms= 70, 1 minute power frequency withstand test voltage of secondary kvrms= 03, total 3creepage distance of bushing mm= 900 mm (minimum), protected creepage distance of bushing mm= 400 mm(minimum), gross weight of pt kg= 70 kg(aprox) [ warranty period 30 months after the date of delivery ]
|